Author : Naser Mohammed Bayoumy AbdelRahim
CoAuthors : Y. Elthokaby
Source : 21st European Conference on Power Electronics and Applications (EPE '19 ECCE Europe), Genova, Italy
Date of Publication : 11/2019
Abstract :
A two-step prediction horizon finite-control set model predictive control scheme is proposed for three phase UPS inverters. Within the control scheme, a constraint is implemented to limit the maximum inverter inrush current, in case of non-linear loads, to an acceptable value. Simulation results show that the proposed control scheme has been successful in limiting the inrush current and producing a load voltage with very low THD with small filter size.